Sizes and Colours
Product
Size
Rolls Per Pack
FI025 Intuflex Wrap
200 mm x 25 mm x 10 m
1
FO400 H&V Foil Tape
100 mm x 50 m
1
50 mm x 50 m
1
75 mm x 50 m
1
Nullifire FI025 Intuflex Wrap
Tested to reinstate up to 120 minutes service insulation (dependent on wall/seal specification) to steel pipes, cable trays, cable ladders, cable baskets, steel trunking and movement sleeves above 0.7 gauge steel.
Nullifire FI025 Intuflex Wrap should be used in conjunction with at least 30-micron FO400 H&V foil tape (not included, available seperately).
Nullifire FI025 Intuflex Wrap is designed to reinstate the insulation requirement where services penetrate a compartment wall or floor. It helps prevent heat passing through pipes, cable trays and services that penetrate a fire barrier wall or floor, Intubatt or Intucompound seals, applying to both sides of the penetration.
Intuflex is a high insulate product, manufactured using fibre manipulation and strand orientation to achieve a compact yet lightweight component. Available in two sizes to accommodate the most onerous service penetrations, Intuflex is finished using reinforced foil offering both an aesthetically pleasing finish and a Class 0 surface spread of flame.
Installation
Intuflex may be cut around service supporting systems to accommodate installation if required.
Nullifire FI025 Intuflex Wrap must be retained using 0.7 gauge (minimum) lacing wire (centrally located) and 50 micron foil tape.
Cable tray ladders
Steel pipes up to 220 mm
Fire Testing
Tested at Exova BM Trada to BS EN 1366 –3
Included within Warrington Certificate CF580 Certifire
IMPORTANT FIRE PRODUCTS NOTICE: The information displayed on this website should be used as a guide ONLY and our Technical Department should be contacted to obtain a tailored specification and any advice necessary before you place an order for fire protection products. Fire protection products are non-returnable except in accordance with Condition 8 of the Terms and Conditions and should be applied only by an individual with the necessary expertise and experience. We will not be held liable for any resulting damage to property, human life or monetary costs incurred due to the incorrect specification you have prepared or use of fire protection products caused by your negligence, including your failure to have contacted us to obtain the relevant advice/specification.